Technical Information

Single Core Cables Copper Conductors

Current ratings for three phase and single phase circuits and volt drop at rated current. Single core Thermosetting insulated unarmoured copper cables with or without sheath to BS7211 or BS5467.

Full thermal ratings: Ambient temperature 30°C Conductor operating temperature 90°C

Conductor Cross-Sectional Area Reference Method 4 (enclosed in conduit in thermally insulating wall etc) Reference Method 3 (Enclosed in conduit on a wall or in trunking etc) Reference Method 1 (clipped Direct) Reference Method 11 (on a perforated cable tray horizontal or vertical) Reference Method 12 (free air)
Horizontal Flat Spaced Vertical Flat Spaced Trefoil
2 Cables, single-phase AC or DC 3 or 4 Cables, three-phase AC 2 Cables, single-phase AC or DC 3 or 4 Cables Three-Phase AC 2 Cable single-phase Ac or DC Flat and Touching 3 or 4 Cables three-phase AC flat and touching or trefoil 2 Cables, single-phase AC or DC Flat and Touching 3 or 4 Cables three-phase AC Flat and touching or Trefoil 2 Cables, single-phase AC or DC or 3 cables three-phase AC 2 Cables, single-phase AC or DC or 3 cables three-phase AC 3 Cables trefoil three-phase
mm² A A A A A A A A A A A
1 14 13 17 15 19 17.5 - - - - -
1.5 18 17 22 19 25 23 - - - - -
2.5 24 23 30 26 34 31 - - - - -
4 33 30 40 35 46 41 - - - - -
6 43 39 51 45 59 54 - - - - -
10 58 53 71 63 81 74 - - - - -
16 76 70 95 85 109 99 - - - - -
25 100 91 126 111 143 130 158 140 183 163 138
35 124 111 156 138 176 161 195 176 226 203 171
50 149 135 189 168 228 209 239 215 274 246 209
70 189 170 240 214 293 268 308 279 351 318 270
95 228 205 290 259 355 326 375 341 426 389 330
120 263 235 336 299 413 379 436 398 495 453 385
150 300 270 375 328 476 436 505 461 570 524 445
185 341 306 426 370 545 500 579 530 651 600 511
240 400 358 500 433 644 590 686 630 769 711 606

VOLTAGE DROP (per ampre per metre):
Conductor operating temperature: 90°C

Conductor Cross-Sectional Area 2 Cables DC 2 Cables, single-phase AC 3 or 4 Cables, Three-Phase AC
Reference methods 3 & 4 (Enclosed in conduit etc. in or on a wall) Reference methods 1 & 11 (Clipped direct or on trays, touching) Reference method 12 (spaced*) Reference methods 3 & 4 (Enclosed in conduit etc. in or on a wall) Reference Methods 1, 11 & 12 (in trefoil) Reference methods 1 & 11 (flat and touching) Reference method 12 (Flat spaced*)
mm² mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1 46 46 46 46 40 40 40 40
1.5 31 31 31 31 27 27 27 27
2.5 19 19 19 19 16 16 16 16
4 12 12 12 12 10 10 10 10
6 7.9 7.9 7.9 7.9 6.8 6.8 6.8 6.8
10 4.7 4.7 4.7 4.7 4.0 4.0 4.0 4.0
16 2.9 2.9 2.9 2.9 2.5 2.5 2.5 2.5
    r x z r x z r x z r x z r x z r x z r x z
25 1.85 1.85 0.31 1.90 1.85 0.190 1.85 1.85 0.28 1.85 1.60 0.27 1.65 1.60 0.165 1.60 1.60 0.190 1.60 1.60 0.27 1.65
35 1.35 1.35 0.29 1.35 1.35 0.180 1.35 1.35 0.27 1.35 1.15 0.25 1.15 1.15 0.155 1.15 1.15 0.180 0.15 1.15 0.26 1.20
50 0.99 1.00 0.29 1.05 0.99 0.180 1.00 0.99 0.27 1.00 0.87 0.25 0.90 0.86 0.155 0.87 0.86 0.180 0.87 0.86 0.26 0.89
70 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.68 0.26 0.73 0.60 0.24 0.65 0.59 0.150 0.61 0.59 0.175 0.62 0.59 0.25 0.65
95 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.49 0.26 0.56 0.44 0.23 0.50 0.43 0.145 0.45 0.43 0.170 0.46 0.43 0.25 0.49
120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.39 0.25 0.47 0.35 0.23 0.42 0.34 0.140 0.37 0.34 0.165 0.38 0.34 0.24 0.42
150 0.32 0.33 0.26 0.43 0.32 0.165 0.36 0.32 0.25 0.41 0.29 0.23 0.37 0.28 0.140 0.31 0.28 0.165 0.32 0.28 0.24 0.37
185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.25 0.25 0.36 0.23 0.23 0.32 0.22 0.140 0.26 0.22 0.165 0.28 0.22 0.24 0.33
240 0.190 0.21 0.26 0.33 0.20 0.160 0.25 0.195 0.25 0.31 0.185 0.22 0.29 0.170 0.140 0.22 0.170 0.165 0.24 0.170 0.24 0.29