Technical Information

Multicore Cables Copper Conductors

Current ratings for three phase and single phase circuits and volt drop at rated current. Twin and multicore PVC insulated unarmoured copper cables with or without sheath to BS6004 or BS7629.

Full thermal ratings: Ambient temperature 30°C Conductor operating temperature 70°C

Conductor Cross-Sectional Area Reference Method 4 (enclosed in conduit in thermally insulating wall etc) Reference Method 3 (Enclosed in conduit on a wall or in trunking) Reference Method 1 (clipped Direct) Reference Method 11 (on perforated cable tray) or reference method 13 (Free Air)
1 Two-Core Cable* Single-Phase AC or DC 1 Three Core Cable* or 1 Four-Core Cable, Three Phase AC 1 Two core cable* Single-Phase AC or DC 1 Three Core Cable* or 1 Four Core Cable, Three-Phase AC 1 Two Core Cable* Single-Phase AC or DC 1 Three Core Cable* or 1 Four-Core Cable, Three Phase AC 1 Two-Core Cable* Single Phase AC or DC 1 Three Core Cable* or 1 Four-Core Cable, Three Phase AC
mm² A A A A A A A A
1 11 10 13 11.5 15 13.5 17 14.5
1.5 14 13 16.5 15 19.5 17.5 22 18.5
2.5 18.5 17.5 23 20 27 24 30 25
4 25 23 30 27 36 32 40 34
6 32 29 38 34 46 41 51 43
10 43 39 52 46 63 57 70 60
16 57 52 69 62 85 76 94 80

* With or without protective conductor

VOLTAGE DROP (per ampre per metre):
Conductor operating temperature:70°C

Conductor Cross-Sectional Area Two-Core Cable DC Two-Core Cable, Single Phase AC Three or Four Core Cable, Three Phase AC
mm² mV/A/m mV/A/m mV/A/m
1 44 44 38
1.5 29 29 25
2.5 18 18 15
4 11 11 9.5
6 7.3 7.3 6.4
10 4.4 4.4 3.8
16 2.8 2.8 2.4

Ambient Temperature Correction Factors

  For Rewireable Fuses Only with PVC Insulated Cable     For all Other Pretective Devices
Ambient Temperature °C 25 30 35 40 45 50 55 60 65     25 35 40 45 50 55 60 65
Correction Factor 1.03 1.00 0.97 0.94 0.91 0.87 0.84 0.69 0.48     1.03 0.94 0.87 0.79 0.71 0.61 0.50 0.35