Armoured Cables Copper Conductors
Current ratings for three phase and single phase circuits and volt drop at rated current. Twin and multicore XLPE insulated armoured copper cables to BS5467 or BS6724.
Full thermal ratings: Ambient temperature 30°C Conductor operating temperature 90°C
| Conductor Cross-Sectional Area |
Reference Method 1 (clipped Direct) |
Reference Method 11 (on a perforated horizontal or vertical cable traycable tray) or reference method 13 (Free Air) |
| 1 Two Core Cable* Single-Phase AC or DC |
1 Three Core Cable* or 1 Four-Core Cable, Three Phase AC |
1 Two-Core Cable* Single Phase AC or DC |
1 Three Core Cable* or 1 Four-Core Cable, Three Phase AC |
| mm² |
amp |
amp |
amp |
amp |
| 1.5 |
27 |
23 |
29 |
25 |
| 2.5 |
36 |
31 |
39 |
33 |
| 4 |
49 |
42 |
52 |
44 |
| 6 |
62 |
53 |
66 |
56 |
| 10 |
85 |
73 |
90 |
78 |
| 16 |
110 |
94 |
115 |
99 |
| 25 |
146 |
124 |
152 |
131 |
| 35 |
180 |
154 |
188 |
162 |
| 50 |
219 |
187 |
228 |
197 |
| 70 |
279 |
238 |
291 |
251 |
| 95 |
338 |
289 |
354 |
304 |
| 120 |
392 |
335 |
410 |
353 |
| 150 |
451 |
386 |
472 |
406 |
| 185 |
515 |
441 |
539 |
463 |
| 240 |
607 |
520 |
636 |
546 |
| 300 |
698 |
599 |
732 |
628 |
VOLTAGE DROP (per ampre per metre):
Conductor operating temperature: 90°C
| Conductor Cross-Sectional Area |
Two-Core Cable DC |
Two-Core Cable, Single Phase AC |
Three or Four Core Cable, Three Phase AC |
| mm² |
mV |
mV |
mV |
| 1.5 |
31 |
31 |
27 |
| 2.5 |
19 |
19 |
16 |
| 4 |
12 |
12 |
10 |
| 6 |
7.9 |
7.9 |
6.8 |
| 10 |
4.7 |
4.7 |
4.0 |
| 16 |
2.9 |
2.9 |
2.5 |
| |
|
r |
x |
z |
r |
x |
z |
| 25 |
1.85 |
1.85 |
0.160 |
1.90 |
1.60 |
0.140 |
1.65 |
| 35 |
1.35 |
1.35 |
0.155 |
1.35 |
1.15 |
0.135 |
1.15 |
| 50 |
0.98 |
0.99 |
0.155 |
1.00 |
0.86 |
0.135 |
0.87 |
| 70 |
0.67 |
0.67 |
0.150 |
0.69 |
0.59 |
0.130 |
0.60 |
| 95 |
0.49 |
0.50 |
0.150 |
0.52 |
0.43 |
0.130 |
0.45 |
| 120 |
0.39 |
0.40 |
0.145 |
0.42 |
0.34 |
0.130 |
0.37 |
| 150 |
0.31 |
0.32 |
0.145 |
0.35 |
0.28 |
0.125 |
0.30 |
| 185 |
0.25 |
0.26 |
0.145 |
0.29 |
0.22 |
0.125 |
0.26 |
| 240 |
0.195 |
0.20 |
0.140 |
0.24 |
0.175 |
0.125 |
0.21 |
| 300 |
0.155 |
0.16 |
0.140 |
0.21 |
0.140 |
0.120 |
0.185 |
Ambient Temperature Correction Factors
For Rewireable Fuses Only with XLPE Insulated Cable
| Ambient Temperature °C |
25 |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
75 |
80 |
85 |
| Correction Factor |
1.02 |
0.98 |
0.95 |
0.93 |
0.91 |
0.89 |
0.87 |
0.85 |
0.79 |
0.69 |
0.56 |
0.39 |
For all Other Protective Devices
| Ambient Temperature °C |
25 |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
75 |
80 |
85 |
| Correction Factor |
1.02 |
0.96 |
0.91 |
0.87 |
0.82 |
0.76 |
0.71 |
0.65 |
0.58 |
0.50 |
0.41 |
0.29 |